Specifications:
GENERAL SPECIFICATIONS
Overall size of the control unit shall be 8"L x 6"W x 4"H, with a
hinged cover on the control box. The enclosure shall be steel with a
NEMA-1 powder coat finish. Two photo-electric eyes shall serve as
sensors, and shall be IR-retro-reflective with a sensing range of six
feet. Sensor target material shall be 1-inch-wide adhesive-backed
retro-reflective tape. A solenoid shall operate the unit's locking
device.
|
Overall size |
8"L x 6"W x 4"H, with hinged cover |
|
Housing |
Steel enclosure with powder coat
finish (NEMA 1) |
|
Sensors |
(2) photo electric eyes, IR
retro-reflective with 6-foot sensing range |
|
Sensor
target material |
1-inch-wide retro-reflective tape
(adhesive backed) |
|
Lock |
Solenoid operated |
ELECTRICAL
SPECIFICATIONS
The door restrictor shall operate on 120VAC power @50mA (typical).
Output shall be rated at 12VDC @500mA (typical). Relay contacts shall
draw 12A @277VAC. Operating range of the photo-electric eyes shall be
12VDC, nominal. A sealed lead-acid battery/charger shall exert 12VDC
@2.9Ahrs. with ratio-metric trickle charger.
| Input requirements |
120VAC @ 50mA (typical) |
|
Output |
12VDC @ 500mA (typical) |
|
Relay
contacts |
12A @ 277VAC |
|
Photo
electric eyes |
10-30 VDC operational range |
|
Solenoid |
12VDC nominal |
|
Battery/charger |
Sealed lead-acid 12VDC @ 2.9 A/hrs with ratio-metric trickle charger |
PERFORMANCE SPECIFICATIONS
The unit shall have an operating range of 20°F to 140°F.
Photo-electric eyes and control board shall be solid state with
indefinite life span. Auxiliary relays and solenoid shall be rated to
withstand no fewer than 10 million operations. Life of the battery
shall be five years.
|
Environmental |
20°F to 140°F |
|
Photo
Electric Eyes |
Indefinite life span (solid state) |
|
Control
Board |
Indefinite life span (solid state) |
|
Auxiliary
Relays |
Minimum of 10 million operations |
|
Solenoid |
Minimum of 10 million operations |
|
Battery
Life |
5 years |
MECHANICAL
SPECIFICATIONS
A 0.4375" steel locking pin shall be coated with a lifetime lubricant.
Battery backup shall be rated for no fewer than four hours. System
shall include a solid-state cooling circuit for high duty-cycle
solenoid operation.
Solenoid operation shall be limited by intelligent on-board logic that
monitors both the Door Zone and Door Position sensors.
Auxiliary relay outputs shall provide 1) Door Zone output for updating
older elevators without Door Zones; and 2) AC Power Loss output with
audible alarm to disable elevator with doors open at next available
landing
Top
|