Motor Full Load Current Table

HP

110-120V 220-240V 440-480V
1/4 5.8 - 2.9 - - -
1/3 7.2 - 3.6 - - -
1/2 9.8 4.0 4.9 2.0 2.5 1.0
3/4 13.8 5.6 6.9 2.8 3.5 1.4
1 16.0 7.2 8.0 3.6 4.0 1.8
1 1/2 20.0 10.4 10.0 5.2 5.0 2.6
2 24.0 13.6 12.0 6.8 6.0 3.4
3 34.0 19.2 17.0 9.6 8.5 4.8
5 56.0 30.4 28.0 15.2 14.0 7.6
7 1/2 80.0 44.0 40.0 22.0 21.0 11.0
10 100.0 56.0 50.0 28.0 26.0 14.0
15 135.0 84.0 68.0 42.0 34.0 21.0
20 - 108.0 88.0 54.0 44.0 27.0
25 - 136.0 110.0 68.0 55.0 34.0
30 - 160.0 136.0 80.0 68.0 40.0
40 - 208.0 176.0 104.0 88.0 52.0
50 - 260.0 216.0 130.0 108.0 65.0
60 - - - 154.0 - 77.0
75 - - - 192.0 - 96.0
100 - - - 248.0 - 124.0
125 - - - 312.0 - 156.0
150 - - - 360.0 - 180.0
200 - - - 480.0 - 240.0
Note: The information in the above table was derived from Table 18 in CSA standard C22.2 # 14, Tables 44 and 45 in CSA standard C22.1 Part 1 and Tables 430-138 and 430-149 in the 1993 National Electrical Code Handbook.  This table is for reference only and complete information should be obtained from the appropriate agency.
Thanks to The Panel Shop for this neat table.

 

 


 